技术参数
|
避雷器使用场所 |
型号 |
系统标称电压有效值
kV |
避雷器额定电压有效值 kV |
避雷器持续运行电压有效值
kV |
直流1mA参考电压
≥ kV |
标称放电电流5kA |
通流容量 |
外形 尺寸图 |
|||
|
陡坡冲击电流残压 峰值 ≤ kV |
雷电冲击电流残压 峰值 ≤ kV |
操作冲击电流残压 峰值 ≤ kV |
2ms方波冲击电流 ≥ A |
4/10us大电流冲击 kA |
|||||||
|
低压型 |
HY1.5W-0.28/1.3 |
0.22 |
0.28 |
0.24 |
0.60 |
- |
1.3 |
- |
50 |
10 |
|
|
HY1.5W-0.5/2.6 |
0.38 |
0.50 |
0.42 |
1.20 |
- |
2.6 |
- |
50 |
10 |
|
|
|
HY1.5W-0.58/3.2 |
0.48 |
0.58 |
0.46 |
1.4 |
- |
3.2 |
- |
75 |
35 |
|
|
|
HY1.5W-0.62/3.6 |
0.52 |
0.62 |
0.5 |
1.6 |
- |
3.6 |
- |
75 |
35 |
|
|
|
HY1.5W-0.8/3.9 |
0.66 |
0.8 |
0.68 |
1.8 |
- |
3.9 |
- |
75 |
35 |
|
|
|
HY1.5W-0.9/4.3 |
0.69 |
0.9 |
0.72 |
1.9 |
- |
4.3 |
- |
75 |
35 |
|
|
|
配电型 |
HY5WS-5/15 |
3 |
5 |
4.0 |
8.0 |
19.6 |
15.0 |
14.5 |
100 |
65 |
|
|
HY5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
34.5 |
30.0 |
25.5 |
100 |
65 |
|
|
|
HY5WS-17/50 |
10 |
17 |
13.6 |
25.0 |
57.5 |
50.0 |
42.5 |
100 |
65 |
|
|
|
线路型 |
HY5WX-5/15 |
3 |
5 |
4.0 |
8.0 |
19.6 |
15.0 |
14.5 |
100 |
65 |
|
|
HY5WX-10/30 |
6 |
10 |
8.0 |
15.0 |
34.5 |
30.0 |
25.5 |
100 |
65 |
|
|
|
HY5WX-17/50 |
10 |
17 |
13.6 |
25.0 |
57.5 |
50.0 |
42.5 |
100 |
65 |
|
|
|
HY5WX51/134 |
35 |
51 |
40.8 |
73.0 |
154.0 |
134.0 |
114.0 |
600/ 800 |
65 |
|
|
|
电 站 型 |
HY5WZ-5/13.5 |
3 |
5 |
4.0 |
7.5 |
15.5 |
13.5 |
11.5 |
200 |
65 |
|
|
HY5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
31.0 |
27.0 |
23.0 |
200 |
65 |
|
|
|
HY5WZ-17/45 |
10 |
上一条:过电压保护器J型、IM型动作计数器
下一条:HSD-FGB系列防爆型大能容智能保护装置
Copyright 2016 安徽森德电气科技有限公司 All Rights Reserved 皖ICP备2023011646号 | |||||||||